Late summer and early fall are when pool lights work hardest. The sun sets earlier, the water is still warm, and evening swims run long. That is also when a lot of pool owners discover a frustrating pattern: flip the pool light off, and the GFCI breaker trips. Or the light shuts itself off mid-swim, then comes back on a few minutes later.
Most people assume the light is shorting out underwater. In modern low-voltage LED systems, that is often not what is happening. This guide walks through pool light GFCI tripping from the ground up: the transformer “kickback” Hayward identifies as the cause of nuisance trips, the snubber capacitor Hayward prescribes to fix it, the thermal cutoff that makes lights cycle on and off, and the brand-specific resets for Hayward, Pentair, and Jandy lights.
- What Really Causes Pool Light GFCI Tripping
- Why a 12V Light Short Won’t Trip Your 120V GFCI
- Symptom-to-Cause Diagnostic Chart
- The Snubber Capacitor Fix, Step by Step
- Thermal Cutoffs: Why Your Light Turns Off and Back On
- Brand-by-Brand Guide: Hayward, Pentair, and Jandy
- Other Causes: Water Intrusion, VFD Pumps, and Voltage Drop
- Diagnostic Readings and Tools
- Parts, List Prices, and DIY vs. Licensed Electrician
- Prevention, Maintenance, and Warranty Traps
- Red Flags That Mean Stop and Call a Pro
You Could Win Free ProTuff Gear — Every Month
No Spam. Unsub anytime. Remain subscribed, remain eligible every month.
What Really Causes Pool Light GFCI Tripping
When a pool light circuit keeps tripping its GFCI (Ground Fault Circuit Interrupter) breaker, the natural assumption is a short to ground inside the underwater fixture. But for 12V lights on an isolation transformer, Hayward’s documentation points somewhere else: inductive arc noise from the low-voltage transformer.
Here is what happens. Your pool light runs on a transformer that steps 120V household power down to 12V or 14V. When that transformer is switched on or off — by a light switch or an automation relay — its “inductive kick” throws a brief arc across the switch contacts.
That arc injects noise into the supply wiring. Hayward’s bulletin 092661 Rev B explains that the noise feeds back to the panel and to every installed breaker. The circuitry inside a GFCI breaker may react to it and trip, even though there is no ground fault current present — sometimes on an unrelated circuit.
Hayward also notes why this got more common: as of June 29, 2015, UL issued major revisions to UL 943, the GFCI safety standard. GFCI breakers must now “auto-monitor” or “self-test,” and that change can make them more susceptible to nuisance tripping.
This is why the classic symptom is so specific: the GFCI trips at the moment you turn the lights off (or on), not while they are simply running.
If your GFCI trips right when the pool lights switch on or off, suspect transformer arc noise first. Hayward’s approved solution is a GLX-HAL-XSNUB snubber capacitor wired across the transformer’s primary leads (line to neutral) on the load side of the light switch or relay.
Other causes are real too: water getting past a lens gasket, moisture from rain or sprinklers, thermal cutoff cycling, and harmonic noise from variable speed pump drives. We cover each one below.
Why a 12V Light Short Won’t Trip Your 120V GFCI
This is the single most misunderstood part of pool light troubleshooting, and it saves hours of hunting in the wrong place.
A pool light isolation transformer provides galvanic isolation. That means there is no direct electrical connection between the 120V primary winding and the 12V secondary winding. Power moves across purely through the magnetic field.
A GFCI works by comparing current on the hot wire to current on the neutral wire. If there is an imbalance of more than about 5 mA, current is leaking to ground somewhere, and it trips. Now picture a 12V light shorting to ground on the secondary side. That fault current has no path back to the GFCI, so the 120V hot and neutral currents stay balanced. The GFCI does not trip.
So on a 12V isolation-transformer system, a GFCI trip points to the primary side: transformer arc noise, a 120V wiring problem, or moisture on the 120V side. And the reverse is also true. If your 12V light dies but the GFCI holds fine, stop hunting for a 120V fault. Look at the fixture fuse (on lights that have one), the driver board, or the transformer’s output instead.
Use the pattern as your first clue. GFCI trips on a 12V system = look at the 120V side (transformer, switch, relay, junction box). Light dead but GFCI holds = look at the 12V side (fixture fuse, driver board, transformer output).
Symptom-to-Cause Diagnostic Chart
Match what you are seeing to the most likely cause, then work the diagnostic step before buying parts.
| Symptom | Most Likely Cause | Diagnostic Step |
|---|---|---|
| GFCI trips right when lights turn on or off | Inductive arc noise from the 12V isolation transformer | Check whether a snubber is installed; if not, add a GLX-HAL-XSNUB across the 120V primary leads. Check enclosures for moisture. |
| GFCI trips randomly while the light is running | Variable speed pump (VFD) harmonics, or moisture from rain or sprinklers | Clamp a milliamp meter around hot and neutral together to check for leakage above 4–5 mA |
| Light turns off, then back on by itself (GFCI never moves) | Automatic thermal switch cycling from temperatures over 105°F | Check water and air temperature; check the voltage against Hayward’s minimum for the cord length |
| Light completely dead, GFCI holds fine | Blown fixture fuse (12V IntelliBrite 5G) or failed circuit board | Check 120 VAC into the transformer and its low-voltage output; inspect the fixture fuse |
| Jandy Infinite WaterColors lights flashing | Lights not powered by the Infinite WaterColors LED Light Controller | Confirm the lights run from the IWCLC300W controller and check its 14 VAC output |
| Hayward ColorLogic lights flicker, change colors, or relays click randomly | OmniLogic light feature assigned to both Pool and Spa | Delete the light feature from the Spa configuration |
The Snubber Capacitor Fix, Step by Step
A snubber is a plastic-film, high-voltage capacitor that suppresses — “snubs” — voltage spikes like the inductive kick from a transformer attached to a switch. Hayward notes these spikes are not harmful to users. But without arc suppression, they make a GFCI more likely to nuisance trip.
Hayward covers this in bulletin 092661 Rev B and in the GLX-HAL-XSNUB owner’s manual (092620). The approved solution is the Hayward GLX-HAL-XSNUB connected across the primary leads (line to neutral) of the transformer, on the load side of the light switch or relay. The snubber also filters high-frequency noise that can throw the controller and ColorLogic lights out of sync with each other.
The GLX-HAL-XSNUB is included in Hayward’s LTBUY11H70, LTBUY11H14, and LTBUY11300 low-voltage transformers. Intermatic PX50, PX100, and PX300 models now include a noise filter capacitor. If you use a different transformer, Hayward recommends a snubber always be installed on all ColorLogic 12V lighting applications.
The snubber connects to the 120V primary side of the transformer. All wiring must follow the National Electrical Code, including Article 680. Shut off power at the breaker and confirm it is dead before touching anything. If you are not qualified to work on line-voltage wiring, have a licensed electrician do this.
Turn off the breaker feeding the light circuit. Use a multimeter to verify zero voltage at the light switch or relay output before you open anything.
Locate the 120V input wires feeding the transformer’s primary, downstream of the light switch or relay.
Connect the GLX-HAL-XSNUB across the transformer’s primary leads — one lead to line, one to neutral — on the load side of the light switch or relay. Follow the wiring diagram in Hayward’s GLX-HAL-XSNUB manual (092620).
Close the enclosure, restore power, and cycle the lights off and on several times. If the GFCI no longer trips on switching, arc noise was your culprit.
Thermal Cutoffs: Why Your Light Turns Off and Back On
Not every “my light keeps shutting off” problem is a GFCI trip. If the breaker never moves but the light goes dark for a while and then comes back on by itself, you are likely looking at the fixture’s automatic thermal switch.
Hayward’s troubleshooting guide says it plainly: depending on cord length and operating voltage, the automatic thermal switch may be cycling due to excessive air or pool water temperatures — over 105°F. The switch cuts power when the fixture gets too hot, then restores it once things cool, so the light cycles instead of staying off.
Running a light out of water causes the same kind of overheating, only faster. Jandy’s manuals warn never to operate an underwater light for more than 10 seconds unless it is totally submerged; without submersion, the light gets extremely hot and the lens or bulb can break. Pentair’s IntelliBrite LED lights carry the same 10-second out-of-water limit (a GloBrite is allowed 30 seconds), because their boards rely on the water to carry heat away.
The ColorLogic Workaround: Pick a Cooler Color
For Hayward ColorLogic lights, Hayward’s documented fix is simple: temporarily switch to a cooler color — Deep Blue Sea, Royal Blue, and so on — until air and water temperatures cool off.
Check that the GFCI is still on. If it is, and the light returns on its own, heat is the likely cause. Check whether the water or air is over 105°F.
On Hayward ColorLogic lights, select Deep Blue Sea or Royal Blue until temperatures come down.
Because Hayward ties thermal cycling to cord length and operating voltage, verify the light is getting the minimum voltage Hayward lists for its cord length (see the voltage drop section below).
Pulling a light onto the deck and switching it on “just to see” is one of the fastest ways to damage it. Never run an underwater light out of water for more than 10 seconds.
Brand-by-Brand Guide: Hayward, Pentair, and Jandy
Each manufacturer handles GFCI noise, thermal protection, and resets differently. Here is what the documentation says for each brand.
- Models covered: Universal ColorLogic (LPCUS, LSCUS), CrystaLogic (LPLUS, LSLUS), ColorLogic 1.5″ (LACUS, LYCUS), ColorLogic 80/40 accent lights (LMCUS, LFCUS), and the Smart Power Transformer (LTSUY11300).
- Sealed lights: Hayward describes the Universal ColorLogic system as sealed, with an unbreakable lens and no serviceable parts. Don’t try to open the fixture.
- GFCI nuisance fix: Install the GLX-HAL-XSNUB snubber across the transformer’s primary leads (line to neutral) on the load side of the switch or light relay. It is already included in LTBUY11H70, LTBUY11H14, and LTBUY11300 transformers.
- Voltage rule: Hayward’s minimum depends on cord length, and its two documents measure in different places. The Universal ColorLogic owner’s manual lists 12–14 volts for a 30 ft cord, 13–14 volts for 50 ft and 14 volts for 100 ft, measured at the transformer with the light on in white mode, and suggests always using the 14V tap when the transformer has one. Hayward’s voltage-drop bulletin gives its minimums at the light cord connection: no less than 12V for 30 ft and 50 ft models, 13V for 100 ft models and 14V for 150 ft models.
- Thermal cutoff: The automatic thermal switch may cycle over 105°F. Switch to Deep Blue Sea or Royal Blue until temperatures cool.
- OmniLogic configuration loop: If a single relay’s light feature is assigned to both Pool and Spa, it creates a control loop that can make ColorLogic lights misbehave. Delete the light feature from the Spa configuration.
- Omni Direct mode: Only Universal ColorLogic lights built after June 2018 support Omni Direct mode. Transformers powering multiple Universal ColorLogic lights must be wired to the same Smart Relay if you want synchronization or Omni Direct mode.
- Models covered: IntelliBrite 5G, GloBrite, ColorVision LED Bubbler, SlimLite, and the Color Sync Controller.
- GloBrite is non-serviceable: Pentair states the complete GloBrite light assembly must be replaced. Original GloBrites used two different materials for the body and the cord end; heat broke the seal and let water in. In 2024, Pentair released an improved GloBrite with a blue gasket and black end cap and updated electronics.
- SlimLite is serviceable: Unlike GloBrite, the SlimLite has a removable circuit board. Use a new lens gasket (P/N 620400Z) every time it is reassembled.
- IntelliBrite 5G fuse: 12V IntelliBrite 5G lights use a replaceable fuse harness (P/N 620276). Pentair notes a new fuse may not fix the problem; if the board is still dead, replace the circuit board — kit 619818Z (color) or 619875Z (300W white).
- IntelliBrite 5G reassembly: Always install a new lens gasket (620400Z) or lens and gasket (619864Z), plus a new Uni-Tension wire clamp assembly, when reassembling. Pentair warns that skipping this can let water leak into the light.
- Controller overload: If both LEDs on the IntelliBrite Controller flash, it has detected a load above its maximum. Reduce the wattage on the controller (300W maximum) and cycle power to reset.
- VFD pump trips: Harmonics from variable speed pump drives can cause false GFCI trips. The Pentair PA220GF (a relabeled Siemens QF220AP, 20A 240V, trips at 6 mA) has added shielding and is meant to be less sensitive to false trips from VS pumps.
- Models covered: WaterColors RGBW, WaterColors White LED, Nicheless LED, Infinite WaterColors, and Laminar Jets.
- Infinite WaterColors needs its own controller: These lights use a digital communication protocol, unlike standard WaterColors. The Infinite WaterColors Nicheless LED Light will not operate when powered from an alternate transformer — it must run from the Jandy Infinite WaterColors LED Light Controller (IWCLC300W), which supplies 14 VAC. If the lights are flashing, confirm they are powered by that controller.
- Nicheless LED voltage, 6W and 12W: 10.7–13.2 VAC on a 100 ft cord; 11.82–13.8 VAC on a 150 ft cord.
- Nicheless LED voltage, 24W: 10.9–13.5 VAC on a 100 ft cord; 11.43–14.1 VAC on a 150 ft cord.
- Color memory (WaterColors and Nicheless): If the light is off for more than 7 seconds, it stays on the current color set when turned back on. To return to the start of the sequence (Alpine White), turn it off, wait 4 to 6 seconds, then turn it back on.
- Controller board: The Infinite WaterColors Light Controller’s replacement PCBA with bracket is kit R0979900. Jandy says service should only be attempted by a qualified pool service professional.
Other Causes: Water Intrusion, VFD Pumps, and Voltage Drop
Water Intrusion and Moisture
Moisture from rain or sprinklers can cause a GFCI to trip. So can water that gets into a light through a worn or reused lens gasket. On serviceable lights like the Pentair IntelliBrite 5G, water intrusion is also a leading way driver boards die.
How you deal with a leaking light depends on the model. Hayward Universal ColorLogic lights and Pentair GloBrite lights are sealed with no serviceable parts, so a flooded one gets replaced. Serviceable lights like the IntelliBrite 5G can be resealed:
Pentair’s manual is blunt: always disconnect power to the pool light at the circuit breaker before servicing it. Turn off both the breaker and the light switch.
Before you start, have a new lens gasket (620400Z) or lens and gasket (619864Z) on hand, plus a fuse assembly (620276) for 12V models.
Remove the pilot screw, lift the light out of the niche to the deck, and remove the Uni-Tension wire clamp and lens.
Install the new gasket and a new Uni-Tension wire clamp assembly. Never reuse the old gasket.
Submerge the assembled light and watch for air bubbles escaping from the gasket area or the cord entrance. If you see bubbles, pull it out and re-seat the gasket and lens. Only finish the install once there are no air leaks.
Variable Speed Pump (VFD) Harmonic Interference
If the GFCI trips at random while the light is running — not at switch-on or switch-off — consider the pump. Harmonics from the variable frequency drive on a variable speed pump can cause false GFCI trips.
Pentair recognized this and recommends special breakers. The Pentair PA220GF is a relabeled Siemens QF220AP with added shielding to resist false trips. Siemens breakers are recommended by some pool equipment manufacturers as the least sensitive to false GFCI trips. Breaker replacement is panel work for a licensed electrician. Also keep the pump dry — not sitting in a puddle or runoff — to help prevent trips.
Voltage Drop and the Wrong Transformer Tap
Long cord runs lose voltage along the way. Hayward sets a minimum voltage that rises with cord length, and ties both thermal cycling and ColorLogic problems to cord length and operating voltage.
Turn the lights on in white mode. Measure AC voltage with a multimeter at the transformer (the point Hayward’s owner’s manual uses) or at the light cord connection in the junction box (the point Hayward’s voltage-drop bulletin uses), and compare it with the minimum for that point.
Hayward lights have a minimum for each cord length: at the transformer in the owner’s manual, and at the light cord connection in the voltage-drop bulletin (see the brand guide). Jandy Nicheless LED lights have their own published window based on wattage and cord length (see the brand guide).
On a multi-tap transformer such as the Hayward LTBUY11300, use the 14V tap; Hayward suggests always using it when the transformer offers one. Cap the unused tap wires with wire nuts.
With the lights running in white, confirm the voltage now meets Hayward’s minimum for your cord length at the point you measured.
Diagnostic Readings and Tools
These are the baseline numbers from the manufacturer and code sources to measure against.
| Parameter | Normal | Problem |
|---|---|---|
| 120V supply at the breaker (Hayward OmniLogic guidance) | 110–130 VAC | Low voltage: correct the power source or breaker |
| Voltage at the transformer or at the light cord connection (Hayward) | At or above Hayward’s minimum for that measuring point and cord length, white mode | Below Hayward’s minimum for that measuring point and cord length |
| Voltage at the light (Jandy Nicheless 6W–24W) | Per wattage and cord length (see brand guide) | Outside the published window |
| GFCI current imbalance | Hot and neutral cancel to zero | A Class A GFCI trips at 4–6 mA |
| Air/water temperature (Hayward thermal switch) | 105°F or below | Over 105°F can cause cycling |
| Controller load (Pentair IntelliBrite Controller) | Up to 300W | Both LEDs flashing = overload |
Tools You Need
- Multimeter: For AC voltage at the breaker, transformer, and light connection.
- Clamp meter that reads milliamps: For the cancelling clamp test below.
- GLX-HAL-XSNUB snubber capacitor: For 12V transformer installs that don’t already have one.
- New lens gaskets: Required any time a serviceable light is opened.
The cancelling clamp test: a clamp meter around both hot and neutral measures the net difference between them. On a healthy circuit, current in both directions cancels and the meter reads zero. If it reads 4–5 mA or more, current is leaking to ground — a real fault, not arc noise.
Parts, List Prices, and DIY vs. Licensed Electrician
The manufacturer documents don’t publish labor rates or typical repair bills, so we won’t guess at them. What Pentair does publish is a lighting parts catalog with list prices. Here are the IntelliBrite 5G parts from Pentair’s 2021 catalog — your dealer’s price today may differ.
| Pentair Part | Description | US List Price (2021 catalog) |
|---|---|---|
| 620276 | Replacement fuse for 12V-only lights | $36.31 |
| 620400Z | Gasket, 8-3/8 in. diameter, silicone | $78.16 |
| 619864Z | Lens and gasket assembly, tempered | $137.38 |
| 79111000 | Uni-Tension wire clamp assembly | $97.76 |
| 619818Z | Light engine kit, color, 2nd generation | $1,258.81 |
| 619875Z | IntelliBrite 5G white LED 300W replacement engine | $956.73 |
Those numbers make one thing clear: a $36 fuse or a $78 gasket is worth trying before a board that lists above $900. It also shows why a proper reseal matters — a reused gasket can flood a light engine worth far more than the gasket.
Who Should Do What
| Task | Who |
|---|---|
| Monthly GFCI test | Homeowner |
| Jandy color reset, ColorLogic cooler-color switch | Homeowner |
| OmniLogic light configuration fix | Homeowner or pool pro |
| Snubber install, transformer tap change | Qualified person only — 120V work inside the transformer or junction box |
| Opening and resealing a serviceable light | Qualified person, power off at the breaker |
| GFCI breaker replacement, new 120V circuits, bonding problems | Licensed electrician |
| Jandy Infinite WaterColors controller service | Qualified pool service professional (per Jandy) |
Never replace lights by splicing wire underwater or behind the niche — Pentair and Hayward both prohibit it, and it is a serious electric shock risk. Extensions or splices are only made in a listed pool/spa junction box or junction box transformer. Never wire LED pool lights to a dimmer.
Prevention, Maintenance, and Warranty Traps
Most pool light GFCI tripping is preventable once you know the mechanisms.
- ☐ Monthly: Test every GFCI. With the breaker handle ON, press TEST. The handle should move to an intermediate “tripped” position. Reset by pushing the handle to OFF first, then ON. If it fails to trip, it must be replaced.
- ☐ Monthly: Look for moisture around junction boxes, transformers, and the pump. Junction boxes must be at least 8 inches above maximum water level or 4 inches above the ground or deck (whichever is higher), and at least 48 inches (4 feet) from the pool’s edge.
- ☐ Any 12V transformer install: Confirm a snubber or noise filter is present — factory-installed or added.
- ☐ Any time a serviceable light is opened: Install a new lens gasket (and a new Uni-Tension wire clamp on IntelliBrite 5G). Leak-test before powering.
- ☐ Heat waves: Run ColorLogic lights on Deep Blue Sea or Royal Blue when temperatures top 105°F.
Water Chemistry Protects the Light, Too
Low pH makes water aggressive and lets equipment and surfaces become etched and corroded. High pH can cause scaly deposits. Keep the water balanced:
| Parameter | Target Range |
|---|---|
| pH | 7.2–7.8 (ideal 7.4–7.6) |
| Total alkalinity | 80–120 ppm |
| Calcium hardness | 200–400 ppm |
| Free chlorine | 1.0–3.0 ppm |
| Cyanuric acid | 30–50 ppm (60–80 ppm for salt pools) |
| Saturation index | -0.2 to +0.2 |
Check Bonding and Grounding While You’re There
Bonding is a continuous loop of bare #8 copper wire connecting the pool’s metal equipment and components, including lights. Separately, when non-metallic conduit is used, an insulated #8 AWG copper grounding conductor runs to the grounding connector inside the niche. That connection must be encapsulated in a listed wet-niche potting compound to protect it from pool water.
What Voids the Warranty (or the Listing)
- Opening sealed fixtures: Pentair GloBrite and Hayward Universal ColorLogic lights have no serviceable parts. Don’t open, service, or tamper with sealed lamps.
- Splices outside a listed box: Cord splices belong only in a listed pool/spa junction box or junction box transformer.
- Dimmer switches: Pentair warns that using a dimmer on IntelliBrite 5G lights causes permanent damage. Hayward and Jandy LED lights also cannot be used with dimmers.
- Jandy internet purchases: Jandy’s limited warranty does not apply to Jandy products bought online or through other e-commerce platforms, except valves under 3 inches in diameter, parts, and accessories. It applies only when installed and serviced by a licensed, qualified contractor where required.
Red Flags That Mean Stop and Call a Pro
Manufacturer warnings are clear: if a GFCI interrupts power without the test button being pushed, ground current may be flowing, indicating the possibility of electrical shock. If your clamp test confirms real leakage, don’t use the equipment. Disconnect it and have a qualified professional correct the problem before anyone swims.
- The GFCI won’t trip when you press TEST: It is defective and must be replaced.
- A cracked lens: Pentair says to replace any cracked lens with a new lens and gasket.
- A damaged light cord: Pentair’s guidance for its Architectural Series lights is that a damaged external cord can’t be replaced — the luminaire is destroyed and replaced.
Frequently Asked Questions
Why does my GFCI trip when I turn my pool light off?
On 12V lights with an isolation transformer, switching the transformer creates an inductive kick that arcs across the switch or relay contacts. That noise feeds back to the panel, and the GFCI’s circuitry can react and trip even with no ground fault. Hayward’s fix is a GLX-HAL-XSNUB snubber across the transformer’s primary line and neutral leads, on the load side of the switch.
Can a short in a 12V underwater pool light trip my 120V GFCI breaker?
No. An isolation transformer has no direct electrical connection between its 120V primary and 12V secondary windings. A short to ground on the 12V side has no path back to the GFCI, so the 120V hot and neutral current stay balanced. If your GFCI trips on a 12V system, look at the primary side instead.
Why does my LED pool light turn off and then come back on by itself?
On Hayward lights, that is usually the automatic thermal switch cycling because air or water temperature is over 105°F, with cord length and operating voltage also playing a role. On ColorLogic lights, switch to a cooler color like Deep Blue Sea or Royal Blue until temperatures cool off, and confirm the voltage meets Hayward’s minimum for your cord length (the Hayward brand guide says where to measure).
How do I reset a Pentair GloBrite light?
Pentair’s GloBrite guide does not list a reset procedure. The light changes shows and colors when its power is switched off and on a set number of times, so follow the chart in the light’s manual. If it still does not respond, have a qualified person check the wiring.
Do Hayward transformers already have a snubber capacitor built in?
Yes, some do. The GLX-HAL-XSNUB is included in Hayward’s LTBUY11H70, LTBUY11H14, and LTBUY11300 low-voltage transformers, and Intermatic PX50, PX100, and PX300 models include a noise filter capacitor. With other transformers, Hayward recommends always adding a snubber on ColorLogic 12V lighting.
Can I put my LED pool lights on a dimmer switch?
No. Pentair warns that using a dimmer on IntelliBrite 5G lights results in permanent damage. Jandy says its WaterColors and White LED lights will not operate properly on dimmers, and Hayward’s ColorLogic replacement lamp cannot be used with dimmers or dimming systems. Wire them to a standard switch or controller.
Why are my Jandy Infinite WaterColors lights flashing?
Infinite WaterColors lights use a digital communication protocol and must be powered by the Jandy Infinite WaterColors LED Light Controller (IWCLC300W), which supplies 14 VAC. They will not operate from an alternate transformer. Jandy’s troubleshooting chart says to confirm the lights are powered by that controller first.